E up to 1.4 MPa
E series boilers with pressure up to 1.4 MPa (solid fuel)
E-1.0-0.9P-3(E), E-2.5-1.4P(E), E-4.0-1.4P(E), E-2.5-0.9P(E)
Description
E series boilers with pressure up to 1.4 MPa (solid fuel). Vertical water-tube double-drum solid fuel boilers E are produced with nominal steam output of 1; 2.5 and 4 tp/h. For solid fuel combustion they are equipped with direct-flow ball furnaces of the corresponding capacities.
Specialist consultation| Indicators | Е-1.0-0.9Р-3(Э) | Е-2.5-1.4Р(Э) | Е-4.0-1.4Р(Э) | Е-2.5-0.9Р(Э) |
|---|---|---|---|---|
| Steam productivity, t/h | 1 | 2.5 | 4.0 | 2.5 |
| Working steam pressure, MPa (kgf/cm2) | 0.8 (8.0) | 1.3 (13) | 1.3 (13) | 0.9 (0.9) |
| Estimated fuel | coal | coal | coal | coal |
| Estimated fuel consumption, at nominal load kg/h, not more than | 147 | 367.6 | 588 | 285 |
| Feed water temperature, °C, not less | 50 | 50 | 50 | 50 |
| Flue gas temperature at the boiler outlet, °C, no more | 320 | 270 | 270 | 270 |
| Efficiency, %, no less | 75 | 80 | 80 | – |
| Boiler weight, kg, no more | 3800 | 14000 | 19000 | 14000 |
| Length, mm, not more | 4200 | 5500 | 5700 | 5500 |
| Width, mm, not more | 2350 | 4000 | 4000 | 4000 |
| Height, mm, not more | 2900 | 4500 | 4500 | 4500 |
| Type of installed furnace | RPK | TSP 2.9 | TSP 5.0 | TSP 2.9 |